VOTRONIC StandBy-Charger Pro installed in the Unimog's technical compartment
← BUILDS & TECHNOLOGY

10 OCTOBER 2026 · ENERGY AUTOMATION

Ready to start.
Even after a long pause.

How a simple idea became a monitored starter-battery automation system using Victron GX, Node-RED, Orion XS and VOTRONIC.

START THRESHOLD≤ 12.5 V for 5 minutesCHARGE CYCLE30 minutesSOC PROTECTIONStop 20% · release 30%

Use the energy already on board before the starter battery becomes a problem.

Our Unimog can remain parked for long periods. Parasitic loads slowly draw energy from the starter battery while the house battery usually still has ample reserve. We did not want jump-starting at the press of a button, but autonomous maintenance charging: react in time, protect both battery systems and make the entire process visible remotely.

01Preserve starting ability

The automation detects gradual discharge after long periods of inactivity.

02Protect the reserve

The house battery only supplies energy while its state of charge allows it.

03Less manual work

Monitoring, switching and follow-up checks run without intervention.

04Make faults visible

GX and VRM show operating states and faults remotely.

Four building blocks. One clearly interlocked task.

The Victron GX system running Venus OS Large supplies the starter voltage, house-battery SOC and device states. Node-RED evaluates these values, runs the timers and decides which charging path may be enabled. VRM provides the remote view.

The Orion XS charges the house battery while driving. When parked, the VOTRONIC StandBy-Charger Pro provides limited maintenance charging for the starter battery. To prevent opposing DC/DC paths from operating together, Node-RED locks the Orion first and waits for confirmation before enabling VOTRONIC.

MEASURE · DECIDE · MONITORVictron GX + Node-RED

Starter voltage · house SOC · timers · feedback · fault states

Remote access and history through VRM
ENERGY RESERVEHouse batterySOC protected
MAINTENANCEVOTRONIConly after release
VEHICLE SIDEStarter batteryvoltage monitored

Interlock: The Orion XS is confirmed off before every VOTRONIC charge and is only released again afterwards.

Installed VOTRONIC StandBy-Charger Pro with control relay in the Unimog's technical compartment
The VOTRONIC StandBy-Charger Pro in the technical compartment: power path, EN control wire and relay are visible at the installation.
Victron GX IO-Extender 150 with active relay and status indicators in the Unimog
The GX IO-Extender turns Node-RED decisions into physical switching signals and supplies the required feedback.

A single threshold would not be enough.

A brief voltage dip must not trigger a charge cycle. The automation needs to debounce measurements, retain AUTO mode through restarts, wait for feedback and stop safely when signals are missing. That is why the process runs as a state machine rather than a loose chain of triggers.

AUTO only means that the automation is allowed to operate. Whether it is waiting, confirming undervoltage, locking the Orion, charging, resting or reporting a fault is a separate state. This keeps its behaviour unambiguous after restarts and delayed device feedback.

Check first. Interlock next. Then charge.

  1. 01
    Read AUTO mode

    The selected operating mode is loaded reliably at startup and retained.

  2. 02
    Confirm undervoltage

    The starter voltage must remain at or below 12.5 V for five continuous minutes.

  3. 03
    Protect house SOC

    Charging stops below 20%; the automation is not released again until 30%.

  4. 04
    Lock the Orion XS

    Node-RED switches the Orion off and waits for confirmed feedback.

  5. 05
    Enable VOTRONIC

    The 30-minute maintenance charge only begins after the interlock is confirmed.

  6. 06
    Switch back cleanly

    VOTRONIC turns off, then the Orion XS is released again.

  7. 07
    Rest for ten minutes

    The starter battery stabilises before the next assessment.

  8. 08
    Repeat if required

    If the starter voltage is still below 12.7 V, another cycle begins.

Emergency reverse charging and automatic maintenance solve different problems.

Victron's emergency reverse charging temporarily reverses the Orion XS charging direction. The 12/12-50A model can supply up to 25 A. It is started manually in VictronConnect, charges in reverse for 15 minutes and then lets the starter battery rest for five minutes. It is practical assistance when starting energy is already insufficient.

Our solution intervenes earlier: it monitors continuously, starts autonomously, respects the house-battery SOC and can repeat after a rest period. VOTRONIC performs the gentle maintenance charge, while the Orion remains available for its main job while driving. The new Victron function therefore does not replace this automation.

Victron documentation on emergency reverse charging ↗

The software switched correctly – yet the charger still did not charge.

In the first version, AUTO did not start by itself. The mode was visible but was not passed to the state machine as a usable event during initialisation. Only a manual OFF → AUTO change produced the required impulse. Once corrected, the switching sequence started reliably.

VOTRONIC then remained physically in standby despite an active GX output. Its own UINLO input threshold was set too high and blocked charging. Only a careful adjustment to the actual switching point brought the software release, relay path and charger together.

SOFTWAREInitialise AUTO

A visible mode is not yet a processed event.

HARDWARECheck UINLO

A switched output does not yet prove real charging current.

Do not turn it blindly to minimum: UINLO and UOUT must suit the battery type, cable losses and desired house-battery reserve. Node-RED's SOC protection complements the hardware protection; it does not replace it.

What matters is whether the complete sequence works without intervention.

The test began at about 12.21 V starter voltage. After five minutes of confirmed undervoltage, the automation locked the Orion, enabled VOTRONIC and began the 30-minute charging phase. Once UINLO had been corrected, charging current actually flowed. VOTRONIC then switched off automatically, the Orion was released and the rest period completed.

START
12.21 V
starter battery
CHARGE TIME
30 min
automatic cycle
FINISH
13.06 V
after the cycle
HOUSE
73.6%
SOC at test end

After ten minutes of rest, no second cycle was needed: the starter voltage was already above 12.7 V. The automation returned to standby.

This is a practical report – not a universal wiring guide.

Work on vehicle batteries can involve very high short-circuit currents, cable fires and damage to control units. Fuses, cable sizes, grounding, battery types and EN/DIS connections must suit the individual system. If in doubt, have a qualified specialist check the installation and final voltage thresholds.

The best automation quietly preserves starting capability.

The decisive factor was not one threshold, but the interaction of measurements, time, interlocking, feedback and hardware protection. The Unimog now uses its available energy deliberately without losing sight of the house reserve – and we can follow the system through GX and VRM.